Cable Size Calculator
BS 7671 cable sizing guidance for domestic circuits — lighting, ring finals, radials, cookers, showers and EV chargers. Applies correction factors and checks voltage drop.
Design current (Ib) will be calculated as W ÷ 230V.
—
Measure the cable route from consumer unit to furthest point. Used for voltage drop calculation.
BS 7671 Guide
How Cable Sizing Works
The three cable sizing criteria
Every circuit cable must satisfy three criteria under BS 7671. First, current-carrying capacity: the cable must carry the design current (Ib) continuously without overheating. Second, voltage drop: the voltage reduction along the cable length must not exceed 3% for lighting or 5% for power circuits. Third, earth fault protection: the earth fault loop impedance (Zs) must be low enough to ensure the protective device disconnects fast enough under a fault.
This tool checks the first two criteria. The third — loop impedance — must be calculated and tested by a qualified electrician on-site as it depends on the supply impedance (Ze) unique to each property.
Correction factors explained
Ca (ambient temperature): Tabulated cable ratings assume 30°C ambient. Above 30°C the cable cannot dissipate heat as effectively — Ca reduces the rated capacity. At 40°C for PVC insulation, Ca = 0.87.
Cg (grouping): Cables touching each other generate mutual heating. Two grouped circuits: Cg = 0.80. Three: 0.70. Six or more: 0.57. Each cable in the group must be sized for its derated capacity.
Ci (thermal insulation): Cable running through thermal insulation cannot dissipate heat. Touching insulation on one side: Ci = 0.75. Fully enclosed in insulation: Ci = 0.50. This halves the effective current rating — avoid burying cables in insulation where possible, or use a significantly larger CSA.
Voltage drop calculation
Voltage drop (Vd) is calculated as: Vd = (mV/A/m) × Ib × L / 1000 where mV/A/m is the millivolt drop per amp per metre for the chosen cable CSA (from BS 7671 Appendix 4), Ib is design current in amps, and L is the one-way cable length in metres.
The result must not exceed 6.9V (3% of 230V) for lighting circuits, or 11.5V (5%) for other circuits. Long runs may require a larger cable CSA than current capacity alone demands — the calculator flags when this is the governing criterion.
FAQ
Common Questions
A standard ring final uses 2.5mm² 6242Y twin and earth. The ring arrangement means both legs are in parallel, giving an effective capacity of 2×27A = 54A — well above the 32A protective device. Voltage drop must be checked for the full ring length, which for a typical 30–40m ring is usually within limits with 2.5mm².
A 9.5kW shower draws approximately 41.3A. With a 45A protective device and typical ceiling void installation (Ci=0.75), 10mm² cable is required. The derated capacity at Ci=0.75 is 65×0.75=48.8A, which exceeds the 45A MCB. Always verify with a qualified electrician for your specific installation conditions.
Yes — larger cables have lower resistance and therefore lower voltage drop per metre. On long runs, voltage drop may require a larger cable than current capacity alone demands. For example, a lighting circuit on a 30m run at 6A current may technically fit 1.0mm², but the voltage drop may require 1.5mm² to stay within the 3% limit.
Part P requires that electrical installation work in dwellings is carried out to BS 7671 standard and either certified by a registered competent person (NICEIC, NAPIT, ELECSA etc.) or notified to local authority building control. Adding new circuits, extending circuits in kitchens or bathrooms, and installing consumer units all fall within Part P scope. Minor additions in dry areas (like adding a socket to an existing circuit) may be exempt.